Page 11 - The 12th Graduate Integrity Conference Proceeding
P. 11
Abstract
From the information shows department of disaster prevention and mitigation ministry. Thailand has
conflagration from fire 1,294 time / year and caused massive losses. When a fire occurred, the chance of burning
the entire building was high due to the spread of the fire from one point to another. The majority of buildings
where a fire occurred was residential and commercial buildings, as these two types of buildings were more
likely to spread a fire than other types of buildings. The most common cause of fires and one of the most
important causes was a damaged power cord as it can lead to a short circuit that was dangerous to human
body and property. From the problem, it was found that the main reason for the fastest deterioration of the
wires was heat. According to the above studies, when the wires began to deteriorate, the following problems
were short circuits leading to fires and fire spreading to other parts. This is the study source of the heat
generation behavior of the electric cable above the ceiling to study the thermal behavior of both conduit and
non-conduit.
From the analysis of this data and the results of this research, it was a pilot study in which the
researcher conducted a specific case study of bare wires and ducting to study the behavior of heat radiated
from the wires during use. The research compared wires' heat radiation in the two experiments over time to
observe the behavior of the radiated heat. This thermal mass was part of the heat resulting in premature failure
of the insulated wire insulation. According to the research, it was found that the temperature increase of both
conduit and non conduit tended to increase in both ways. Non conduit wires can dissipate heat better and
faster, so the insulation temperature on the cord is not as hot as the wires being routed through the conduit.
However, from this experiment, it was found that the heat and ventilation problems from the wires were
radiated around which the heat being drained from the wires could not be discharged from the conduit. From
the results of the experiment, in the first 10 minutes, the heating temperature was not much different, but after
60 minutes, the temperature of the conduit wire began to rise above 2 degrees. After 240 minutes, the
temperature of the conduit wires was 6.5 degrees higher with 35.7 degrees in the conduit, resulting in a higher
temperature inside the pipe than the conduit. This led to problems as the wire insulation deteriorated faster
than it should. In this experiment, the experiment was performed in an air-conditioned room at 25 degrees,
resulting in the resulting data from the temperature not as high as it actually was under a roof that was heated
by the sun. The results of this study can be used to guide the development of design work for further
prevention.
Keywords: Conduit, Ceiling, Insulated wire, Deterioration, Thermal Behavior
1. บทนำ
็
จากสถิติเพลิงไหมในประเทศไทยพบวา หนึ่งในสาเหตุหลัก ที่ทำใหเกิดเพลิงไหมคือสายไฟชำรุดในบริเวณที่มองไมเหน
เชนบริเวณเหนือฝาเพดาน โดยรูปแบบการเดินสายไฟฟาที่ใชในบานพักอาศัยสวนใหญในประเทศไทย นิยมติดตั้งสายไฟฟาอย ู
ี
ี
ดวยกัน 2 แบบ คือวิธติดตั้งสายไฟฟาอยูเหนือฝาเพดาน และวิธติดตั้งสายไฟฟาแบบเดินลอย ในปจจุบันบานพักอาศัยสวนใหญ
ิ
่
นิยมวิธีการตดตั้งระบบสายไฟฟาอยูเหนือฝาเพดาน เนื่องจากเปนวิธีทีเรียบรอย เพราะมองไมเห็นจากภายนอก จากปญหาพบวา
็
สาเหตุหลักที่ทำใหสายไฟเสื่อมสภาพไดเรวทีสุดคือความรอน การศึกษาขางตนเมือสายไฟเริ่มเสื่อมสภาพ ปญหาที่ตามมาคอการ
่
ื
่
ิ
เกิดการลัดวงจรและนำไปสการเกิดเพลิงไหมและการลามไฟไปยังสวนอื่น จึงเปนที่มาของ การศึกษาพฤตกรรมการเกิดความรอน
ู
บริเวณสายไฟฟาเหนือฝาเพดาน เพื่อศึกษาเปรียบเทียบพฤติกรรมการเกิดความรอนของสายไฟทั้งแบบรอยทอนำสายไฟ และ
ไมรอยทอนำสายไฟ
2